Fill in the search criteria to search the database or view index of all documents.

climates

Very Cold - A very cold climate is defined as a region with approximately 9,000 heating degree days or greater (65°F basis) or greater and less than 12,600 heating degree days (65°F basis).

Cold - A cold climate is defined as a region with approximately 5,400 heating degree days (65°F basis) or greater and less than approximately 9,000 heating degree days (65°F basis).

Mixed-Humid - A mixed-humid and warm-humid climate is defined as a region that receives more than 20 inches of annual precipitation with approximately 4,500 cooling degree days (50°F basis) or greater and less than approximately 6,300 cooling degree days (50°F basis) and less than approximately 5,400 heating degree days (65°F basis) and where the average monthly outdoor temperature drops below 45°F during the winter months.

Hot-Humid - A hot-humid climate is defined as a region that receives more than 20 inches of annual precipitation with approximately 6,300 cooling degree days (50°F basis) or greater and where the monthly average outdoor temperature remains above 45°F throughout the year. This definition characterizes a region that is similar to the ASHRAE definition of hot-humid climates where one or both of the following occur:

  • a 67°F r higher wet bulb temperature for 3,000 or more hours during the warmest six consecutive months of the year; or
  • a 73°F or higher wet bulb temperature for 1,500 or more hours during the warmest six consecutive months of the year.

Hot-Dry/Mixed-Dry - A hot-dry climate is defined as region that receives less than 20 inches of annual precipitation with approximately 6,300 cooling degree days (50°F basis)or greater and where the monthly average outdoor temperature remains above 45°F throughout the year.

A warm-dry and mixed-dry climate is defined as a region that receives less than 20 inches of annual precipitation with approximately 4,500 cooling degree days (50°F basis) or greater and less than approximately 6,300 cooling degree days (50°F basis) and less than approximately 5,400 heating degree days (65°F basis) and where the average monthly outdoor temperature drops below 45°F during the winter months.

Marine - A marine climate meets is defined as a region where all of the following occur:

  • a mean temperature of the coldest month between 27°F and 65°F;
  • a mean temperature of the warmest month below 72°F;
  • at least four months with mean temperatures over 50°F; and
  • a dry season in the summer, the month with the heaviest precipitation in the cold season has at least three times as much precipitation as the month with the least precipitation.

information

Building Science Insights are short discussions on a particular topic of general interest. They are intended to highlight one or more building science principles. The discussion is informal and sometimes irreverent but never irrelevant.

Building Science Digests provide building professionals from different disciplinary backgrounds with concise overview of important building science topics. Digests explain the theory behind each topic and then translate this theory into practical information.

Published Articles aare a selected set of articles written by BSC personnel and published in professional and trade magazines that address building science topics. For example, our work has appeared in Fine Homebuilding, Home Energy, ASHRAE's High Performance Buildings, The Journal of Building Enclosure Design and The Journal of Building Physics. We thank these publications for their gracious permission to republish.

Conference Papers are peer-reviewed papers published in conference proceedings.

Research Reports are technical reports written for researchers but accessible to design professionals and builders. These reports typically provide an in-depth study of a particular topic or describe the results of a research project. They are often peer reviewed and also provide support for advice given in our Building Science Digests.

Building America Reports are technical reports funded by the U.S. Department of Energy (DOE) Building America research program.

Designs That Work are residential Case Studies and House Plans developed by BSC to be appropriate for residential construction in specific climate zones. Case Studies provide a summary of results for homes built in partnership with BSC’s Building America team. The case study typically includes enclosure and mechanical details, testing performed, builder profile, and unique project highlights. House Plans are fully integrated construction drawing sets that include floor plans, framing plans and wall framing elevations, exterior elevations, building and wall sections, and mechanical and electrical plans.

Enclosures That Work are Building Profiles and High R-Value Assemblies developed by BSC to be appropriate for residential construction in specific climate zones. Building Profiles are residential building cross sections that include enclosure and mechanical design recommendations. Most profiles also include field expertise notes, material compatibility analysis, and climate challenges. High R-Value Assemblies are summaries of the results of BSC's ongoing High R-Value Enclosure research — a study that BSC has undertaken for the U.S. Department of Energy (DOE) Building America research program to identify and evaluate residential assemblies that cost-effectively provide 50 percent improvement in thermal resistance.

Guides and Manuals are "how-to" documents, giving advice and instructions on specific building techniques and methods. Longer guides and manuals include background information to help facilitate a strong understanding of the building science behind the hands-on advice. This section also contains two quick, easy-to-read series. The IRC FAQ series answers common questions about the building science approach to specific building tasks (for example, insulating a basement). The READ THIS: Before... series offers guidelines and recommendations for everyday situations such as moving into a new home or deciding to renovate.

Information Sheets are short, descriptive overviews of basic building science topics and are useful both as an introduction to building science and as a handy reference that can be easily printed for use in the field, in a design meeting, or at the building permit counter. Through illustrations, photographs, and straightforward explanations, each Information Sheet covers the essential aspects of a single topic. Common, avoidable mistakes are also examined in the What's Wrong with this Project? and What's Wrong with this Practice? mini-series.

Videos.

Information Sheets
Armin Rudd

The performance of the cooling system will be evaluated and assured through a series of measurements including: air flow, pressures, temperatures, humidity levels, and power draw. To get off to the best start possible, the following procedures (or...
Information Sheets

Ventilation system intakes must be sufficiently separated away from potential contaminant sources, and locations of dust and debris. Mechanical sealed combustion equipment intake should also be located away from likely sources of dust and debris....
Information Sheets

The Manual J (i.e. heating and cooling load) calculations typically yield the airflow requirements to the various rooms to meet those design loads. These airflow volumes are then used to size and lay out the ducts.With any distribution system, there...
Information Sheets

Ductwork, furnaces and air handlers should be sealed against air leakage. The only place air should be able to leave the supply duct system and the furnace or air handling unit is at the supply registers. The only place air should be able to enter...
Information Sheets

The location of the duct system can have a significant impact on the overall performance of the system—both the utility use and the ability to provide comfort. The energy loss from the ducts for forced air heating and cooling systems can be...
Information Sheets

These systems are completely decoupled from the interior environment through the use of dedicated outdoor air intake and exhaust ducts connected directly to the unit. This change completely disconnects the combustion process from the interior...
Information Sheets

In climates where the average monthly temperature for the coldest month of the year goes below 45°F, the temperature of the slab perimeter may be below the dew point of interior air for a significant period of time. Even when condensation conditions...
Information Sheets

Crawlspaces should be designed and constructed as mini-basements.  Crawlspaces should not be vented to the exterior (see FAQ on Crawlspace Venting). They should have their floors uninsulated, the ground vapor sealed, their walls insulated and air...
Information Sheets

Basements are part of a home, within the building boundary—despite repeated attempts over the years to disconnect them from the living space. Because of this, basements should be designed and constructed to be dry and conditioned. This is...
Information Sheets

Polyisocyanurate insulation is a common commercial and residential roof and wall insulation. It has one of the highest R-values per inch of thickness among common insulations.However, labeled R-value differs from in-service R-value for many...
Very ColdCold
Information Sheets

Cavity insulation combined with insulating sheathings are common in residential wall construction. Cavity insulations can be categorized as rolled batt; blown-in or loose-fill (fibrous insulation—cellulose, fibreglass, rock or slag wool—supported by...
Information Sheets

 The information presented has been compiled from:ASHRAE Fundamentals - 2001Moisture Control in BuildingsCMHCNRC/IRCIEA Annex 24Manufacturer dataWhen using this information, it MUST be done in the following context:Some of these properties are...
Information Sheets

In building air barriers, the field of the opaque wall typically does not contribute strongly to the building’s overall air leakage.  Instead, details that connect building components are often the cause of much of the air leakage, such as the roof-...
Information Sheets

Some common locations for large holes in the air barrier include bathtubs, showers, fireplace enclosures, and chimneys. Holes behind tub and shower enclosures are common, as these enclosures are often installed before the interior-side air barrier...
Information Sheets

Windows are elements of the building enclosure system that perform many building enclosure functions. One of the building enclosure functions that windows must fulfill is that of an air barrier. As a component of the air barrier system, the...
Information Sheets

Typical penetrations through the primary components of the air barrier system include plumbing pipes and vents, electrical wires and conduits, electrical fixtures, other mechanical services, and, in some cases, structural members.Penetrations...
Information Sheets

Gypsum board drywall is, itself, a suitable air barrier material. The taping of drywall seams results in a plane of airtightness at the field of the wall. However, several steps must be taken to use this material property to create a continuous and...
Information Sheets

Good design and practice involve controlling the wetting of building assemblies from both the exterior and interior and different climates require different approaches.Vapor Permeance CharacteristicsThe vapor permeance characteristic of the...
Information Sheets

As they are typically used in buildings today, vapor barriers are a cold climate artifact that has migrated into other climates more from ignorance than need. However, they often prevent assemblies from drying. Vapor barriers installed on the...
Information Sheets

The requirements in the code can be used for wood framed structures with temperature and humidity conditions typical of residential occupancy.Three classes of vapor control are defined depending on the vapor permeance of the vapor control layer....

Pages