Designs That Work
Hot-Dry / Mixed-Dry Climate: Tucson Profile
PDF
Version
Cross Section

Construction Recommendations
- Foundation: Slab-on-grade
-
Above Grade Wall: Wood frame
-
Cladding: Stucco
-
Attic: None
-
Roof: Membrane
Building Science Notes
- Ducts in conditioned space - This building profile is designed
to accommodate HVAC equipment and ducts in the living space, specifically
in dropped soffits and a utility space in the building core. HVAC ducts
should not be run in exterior walls or the slab.

Figure 19 |
- Air sealing details at transitions – Air sealing can be
particularly difficult, but no less important, at assembly transitions
such as top-of-wall/roof assembly junctions and between attached garages
and living spaces. These are discussed below because they have proven to
be a consistent challenge for high performance production builders.
- Top-of-wall/roof assembly junction – The continuity of an exterior air
barrier can be maintained at this junction if the air barrier material
(foam insulation or stucco cladding, for example) is used continuously for
the wall, soffit, and fascia. The continuity of an interior air barrier
can be maintained through a combination of cut foam blocks and
sealant/caulk, or spray foam. Note that neither cellulose nor fiberglass (batt
or blown) can be used for the air barrier.
- Attached garages – The building enclosure surfaces shared between conditioned space and an unconditioned
garage must have a continuous air barrier. See Figure 19 at right
and
Air Sealing Details
for details in terms of using sealants and rigid insulation to create a
continuous air barrier between the attached garage and living space.
- Drying mechanisms – In any climate, vapor control is based on
the relationships among the following: the permeability of wall
components, the type of cladding (reservoir or non-reservoir), the
presence/lack/nature of an air space, and the magnitude/duration of the
vapor drive (based on the relationship between the exterior and interior
moisture content and temperature differences). The type of sheathing and
housewrap used in any wall assembly must be based on an understanding of
these inter-relationships. See “Insulations,
Sheathings, and Vapor Diffusion Retarders” for more information. This
wall assembly permits drying to both the interior and the exterior
(depending on the selection of exterior sheathing – see the
Building
Material Properties Table).
- Drainage plane, air barrier, and vapor control – The drainage
plane in this wall assembly is the Dupont StuccoWrap®
weatherlapped onto the OSB structural sheathing (the paper-backed lath
serves as the bond break for the stucco cladding). An annual precipitation
of 8 inches (30-year average for Tucson) means that a face sealed stucco
cladding can work, but this system is designed with a drainage plane as a
“belt and suspenders” approach for long-term durability.
The air barrier is the interior gypsum board installed using the Airtight
Drywall approach (see
Air Sealing Details).
The OSB sheathing in this wall assembly limits drying potential to the
exterior, as does the membrane in the "flat" roof assembly. So interior
sheathing and finish components must be selected that promote drying to
the interior.
- Rough opening flashing – Window and door flashing details are
wall assembly or cladding specific and depend on whether the windows are
installed before or after the drainage plane. Refer to the EEBA Water
Management Guide for more information at the
EEBA Bookstore.
- Advanced framing – This wall assembly employs all of the
advanced framing methods except alternative shear resistance; that is,
structural sheathing is used. See
Advanced
Framing Details.
- Framing on slabs – Installing a capillary break between the
sill plate and a concrete slab on all walls—exterior, interior,
partition—is good practice. A closed cell foam sill sealer or gasket works
well. Alternatively, a strip of sheet polyethylene can be used. This
isolates the framing from any source of moisture that may be either in or
on the concrete slab (and using sill sealer on all walls maintains wall
height exactly the same).
- Soil gas ventilation – The sub-slab to roof vent system handles
conditions that are difficult if not impossible to assess prior to
completion of the structure—resultant confined concentrations of air-borne
radon, soil treatments (termiticides, pesticides) methane, etc. The cost
of this “ounce” of prevention is well balanced against the cost of the
“pound” of cure.
- Sub-slab stone bed - The four-inch deep, 3/4-inch stone bed
functions as a granular capillary break, a drainage pad, and a sub-slab
air pressure field extender for the soil gas ventilation system. Without
it, a soil gas ventilation system is not practically possible and the only
capillary break between the slab and ground is the polyethylene vapor
barrier.
- Thermal barrier – In all but the slab foundation, the thermal
barrier is accomplished by cavity insulation. BSC recommends slab
perimeter insulation for all slabs, regardless of the heating or cooling
load, because the slab perimeter represents a significant thermal bridge
that not only affects energy use but also contributes to localized thermal
comfort and potential condensation problems. See Termite Control under
Field Experience Notes for the rigid insulation detail.
- Roofing – Light-colored membrane roofing performs better than
conventional dark colored membrane roofing in this climate. See
Energy Star's Roof Products List for more information.
Climate Specific Details
- Mechanical systems
- Heating – Sealed combustion hot air furnace. Sealed combustion means
that the unit can be located within the conditioned space with no
compromise in indoor air quality or combustion safety.

Figure 20 |
- Cooling - Evaporative cooling is prevalent in Hot-Dry Climates. We
recommend refrigerant cooling in high performance homes in this climate
region for three reasons:
- Refrigerant cooling permits year-round controlled ventilation;
evaporative cooling does not.
- Evaporative cooling can be prone to moisture and indoor air
quality problems without frequent and diligent system maintenance,
refrigerant cooling is not.
- While there can be a slight energy penalty with refrigerant
cooling in comparison to evaporative, this penalty must be balanced
against the year-round comfort provided by refrigerant cooling
(evaporative cooling has difficulty supplying comfort in high humidity
situations), and the substantial water savings associated with
refrigerant cooling (a growing issue in mixed-dry climates).
Follow appropriate sizing procedures. See Figure 20 and the
Cooling System Sizing Pro.
- Ducting - Single return requires transfer grilles to provide path
and avoid pressurizing bedrooms, as shown in Figures 21a-d.
Appropriate sizing for ducts, including these pressure relief methods,
can be found here in the
Cooling System Sizing Pro.

Figure 21a-d
- Controlled mechanical ventilation - Intermittent
central-fan-integrated supply, designed to ASHRAE 62.2P rate, with fan
cycling controls set to operate the central air handler as much as 33% of
the time, but not less than 25 % of the time, occurring within at least
every three hours to provide ventilation air distribution and whole-house
averaging of air quality and comfort conditions (installed cost: $125 to
$150). Include a normally-closed motorized damper in the outside duct with
the AirCycler FRV control (installed cost: $50 to $60). For more
information on controlled mechanical ventilation, see
controlled mechanical
ventilation for more information.
- Termite management – Termites are best managed with a
three-pronged approach that deals with the three things termites
need—cover from sunlight, moisture, and food (wood or paper):
- Reduced cover – Keep plantings 3 feet away from the building
perimeter, thin the ground cover (wood mulch or pea stone) to no more
than two inches depth for the first 18 inches around the building, and
maintain any termite inspection zone on the exterior of the foundation
above grade.
- Control moisture – Maintain slope away from building as shown, carry
roof load of water at least three feet away from building, and make sure
that irrigation is directed away from the building.
- Chemical treatment – Use an environmentally-appropriate soil
treatment (such as Termidor®) and a building materials treatment (such
as Bora-Care®) for termite-prone near-grade wood materials.
- Inter-relationship of first three points – Since a builder and a
homeowner’s ability to employ or stick to each of the three strategies
above will vary, make sure that an inability to fully employ one
strategy is compensated for by complete rigor with the others. For
example, if for some reason, chemical treatment of soil or building
materials is not an option, then complete rigor in moisture control and
ground cover is required.
- Landscaping for wildfire control – keeping woody materials of
any type, living or otherwise, away from the building is good practice in
dry climates where wildfire presents a significant risk.

Figure 22 |
Field Experience Notes
- Termite control – Local codes and interpretations by building
inspectors can make details involving slab insulation difficult. We have
found that building officials accept the flashing/fibercement board shown
in the building profile and in Figure 22.
- HVAC commissioning – The most efficient equipment means little
if the system is not set up and started up properly. Follow
high performance start-up procedures. In dry climates, it is generally
a good idea to set up the air distribution fan to run a little longer at
the end of each cycle to bump up the sensible efficiency.
- Location of HVAC outdoor unit – It’s tempting to put the
condenser right on the roof where the evaporative cooling unit was,
particularly when lot lines are really tight. We do not recommend rooftop
location of the condenser for the following reasons: it makes even routine
maintenance more difficult; it puts the unit at what is most likely the
hottest spot on the entire property; and it introduces more roof
penetrations.
- Advanced framing - For a technical resource that may help with
resistance to advanced framing methods from local code officials, see the
Building Safety Journal article written by Nathan Yost of BSC.
- Slabs – In dry climates, it is quite common for builders to use
a sand layer in between the polyethylene sheet and the cast concrete to
prevent differential drying and cracking problems. This moisture-holding
layer should never be placed between the poly and concrete. Differential
drying and subsequent cracking should be handled with a low water content
concrete and wetted burlap covering. See this
technical
resource for more information.

Figure 23 |
- Moving this assembly to Mixed-Dry climates – This “flat-roof”
assembly is routinely moved to colder climates without any change in the
design/construction of the assembly. We recommend that in any climate
where the average monthly temperature for the coldest month drops below 45°F,
one of the following four methods be employed to significantly reduce the
potential for condensation problems in the structural roof deck (see
Figure 23):
- Adding rigid insulation above the roof deck to raise the temperature
of the roof deck to control condensation. Rigid polyisocyanurate
insulation is recommended for its temperature stability. The amount of
rigid insulation required is calculated by the climate location. See “Insulations,
Sheathings and Vapor Diffusion Retarders."
- Spraying rigid foam insulation on the underside of the roof deck and
cover with fiberous cavity insulation. The thickness of the spray foam
insulation is calculated as in #1 above.
- Locating all of the insulation above the roof deck.
- Spraying the entire cavity with foam insulation.
Material Compatibility and Substitutions
- Interior latex paint - The substitution of low permeability
interior finishes (vinyl wall paper, oil-based paints) for latex paint is
strongly discouraged as drying to the interior is important in mixed
climates.
- Building papers with stucco – There must always be two
components here—the bond break material and the drainage plane. Although
StuccoWrap® is advertised as both a drainage
plane material and the layer receiving the stucco, these two materials
should never be combined or reversed in this assembly.
- Exterior sheathing materials – In this assembly, the reservoir
cladding means that a moisture sensitive material such as fiberboard
should not be used. Plywood is an acceptable substitution for OSB in this
wall assembly. For more information, see the Building Materials Property
Table or “Insulations, Sheathings
and Vapor Diffusion Retarders.”
- Cavity insulation materials – Acceptable cavity insulation
includes any that have a relatively high vapor permeability—cellulose,
fiberglass, foam (as long as air sealing is accomplished by a separate
component or system when cellulose or fiberglass is used). User discretion
can be based on properties other than building science.
- Flooring - Because curing concrete releases significant
moisture for several months after being cast, we recommend that a low w/c
concrete ratio (< 0.45) be used to protect the integrity of finished
flooring. We recommend that vinyl flooring not be installed over a
concrete slab.
- Gypsum wallboard – Areas of potentially high moisture, such as
bathrooms, basements, and kitchens, are excellent candidates for non-paper
faced wallboard systems (e.g. James Hardie’s Hardibacker®,
GP’s DensArmor®, USG’s Fiberock®).
In addition, paper-faced gypsum board should never be used as interior
sheathing or backer for tub or shower surrounds where ceramic tile or
marble (any material with joints or grout lines) is used as the finish.
|
|