
BSC
Building America Performance Criteria
Requirements: Design
- Residences must reduce whole house energy use (HVAC, hot water,
lighting, and all appliances/plug loads) as stipulated in the table
below:
|
Project Type |
Percent1
Reduction |
Energy Star2
Index |
|
Single Homes |
40% |
60-65 |
|
Communities |
30% |
70-75 |
- Whole-house dilution ventilation: a mechanical ventilation
system must be installed to be capable of meeting ASHRAE Standard
62.2 which stipulates a ventilation rate of 7.5 CFM per person
(counted as the number of bedrooms plus one) plus 0.01 CFM per
square foot of floor area. While 62.2 stipulates that operation of
the ventilation system is at the occupant’s discretion and the
Standard is silent regarding whole-house distribution of ventilation
air, this Performance Criteria stipulates that the 62.2 ventilation
flow rate be delivered at least one-third of the time and that
whole-house distribution is required.
- Local exhaust ventilation: Intermittent spot exhaust of 100 CFM
must be provided for each kitchen (no recirculating cooktop hoods).
Intermittent spot exhaust of 50 CFM or continuous exhaust of 20 CFM
when the building is occupied must be provided for each room having
a toilet, bath, or shower.
- Ventilation intake locations: When a supply-only or balanced
ventilation system is used, the intake must go through an outside
wall and not the roof (due to proximity to exhaust/vent pollutants,
and heated air/VOC's/odors from the roof). Wall intakes should be
located at least 10 feet from, and not directly above, any wall
exhaust or vent.
- All combustion appliances (except a gas stove or cooktop) in the
conditioned space must be sealed combustion. Specifically, any
furnace inside conditioned space must be a sealed-combustion 90%+
unit. Any water heater inside conditioned space must be direct-
power-vented. Any boiler inside a conditioned space must be sealed
combustion.
- Windows with the following climate-specific performance values
must be used:
| Climate Zone3 |
Maximum
U-Value |
Maximum
SHGC |
| Zones 1-3 |
0.40 |
0.35 |
| Zones 4-8 |
0.35 |
0.40 |
- All ducts and air handling equipment must be in the conditioned
space.
- Major appliances (refrigerator, clothes washer, and dishwasher)
must achieve Energy Star performance in the top one-third of the DOE
Energy Guide rating scale.
- All lighting must be Energy Star qualified with the following
exceptions: motion-sensitive outdoor spotlights and solar-powered
accent and pathway lighting. LED technology is currently not
certified by Energy Star, however LEDs are acceptable.
- Carbon monoxide detectors (hard-wired units) must be installed
(at one per every approximate 1000 square feet) in any house
containing combustion appliances, and/or an attached garage.
Requirements: Testing
- Building America testing of the house must be completed as part
of the commissioning process. The SNAPSHOT form is a testing
template and is available for download to record the testing
information (Snapshot
Form). Instructions for completing the form are also available
(Snapshot
Instructions).
- In a production setting, each model type (i.e., floor plan) must
be tested until two consecutive houses of this model type meet
testing requirements. Additional, testing on this model type can be
reduced to a sampling rate of 1 in 7 (i.e., 1 test, with 6
"referenced" houses). Small additions to a floor plan (e.g., bay
window, conversion of den to bedroom) are considered to be the same
model type; major changes (e.g., bonus room over the garage,
conversion of garage into a hobby room, etc) must be considered a
separate model type. Unique or custom house plans must each be
individually tested.
- Air leakage (determined by pressurization testing) must be less
than 2.5 square inches/100 square feet surface area leakage ratio (CGSB,
calculated at a 10 Pa pressure differential); or 1.25 square
inches/100 square feet leakage ratio (ASTM, calculated at a 4 Pa
pressure differential); or 0.25 CFM/square foot of building
enclosure surface area at a 50 Pascal air pressure differential. The
calculation of the building enclosure area includes the foundation
or below-grade surface areas. If the house is divided into multiple
conditioned zones, such as conditioned attics or conditioned crawl
space, the blower door requirement must be met with the access to
the space open, connecting the zones.
- Total space conditioning system duct leakage must be less than
five percent of the total air handling system rated air flow at high
speed (nominal 400 CFM per ton) determined by pressurization testing
at 25 Pa. Two compliance mechanisms are acceptable: (1) test total
duct leakage at finish stage, or (2) test total duct leakage at duct
rough-in stage. When more than one air handler exists, each air
handling system must individually meet the requirement. If zoning is
used, all zone dampers must be open. Manual or motorized outside air
ventilation dampers must be closed.
- Local and whole-house mechanical ventilation system airflows
must be tested during commissioning of the building.
- Forced air systems that distribute air for heating must be
designed to provide balanced airflow to all conditioned spaces and
zones (bedrooms, hallways, basements). Inter-zonal air pressure
differences, when doors are closed, must be less than 3 Pa using
passive transfer grilles or jump ducts, or active return ducts (see
Transfer Grille Detail and
Transfer Grille Sizing Chart).
Recommendations: Mechanical
Equipment
- System external static pressure must be within manufacturer
specifications (0.5 WIC/125 Pa maximum typical).
Recommendations: Energy
Conservation, Occupant Comfort
- Information relating to the safe, healthy, comfortable operation
and maintenance of the building and systems that provide control
over space conditioning, hot water or lighting energy use should be
provided to occupants.
- The building enclosure and mechanical systems design should be
capable of maintaining comfortable conditions throughout the
conditioned space as defined by ASHRAE Standard 55-2004 (Thermal
Environmental Conditions for Human Occupancy).
- Indoor humidity should be maintained in the range of 25 to 60
percent by controlled mechanical ventilation, mechanical cooling, or
supplemental dehumidification. In very cold, cold, and mixed
climates (Zones 4 through 8) during the winter, indoor relative
humidity should be kept on the lower end of that range (see article
"Relative
Humidity" for guidelines).
Recommendations: General
Construction
- The building enclosure and sitework design and construction
should provide effective drainage measures to prevent moisture
intrusion, conveying water off of and away from the building.
- Design and construct the building foundation to prevent the
entry of moisture and other soil gases.
- Building assemblies should be designed and constructed to permit
drying of interstitial spaces.
- Design and construct building assemblies to prevent or control
airflow into insulation systems from both the interior and exterior.
- Use radon resistant construction practices as referenced in the
ASTM Standard "Radon Resistant Design and Construction of New Low
Rise Residential Buildings.
- Provide filtration systems for forced air systems that provide a
minimum MERV of 11 or higher.
Recommendations: Green
Building
|
|